Transmission Line Insulators

Insulator Section View 4
Insulator Specifications Table

Transmission line insulators : Suspension and Tension Application as per IEC 61109 , IEC 62217 & IEC 60815

Nominal System Voltage (kV) Min Creepage Distance (mm) Sectional Length (mm) Mechanical Load (kN) Wet Power Frequency Withstand Voltage (kV) Dry Lightning Impulse Withstand Voltage (kV) Type of End Fitting
66224872570/90140350Ball & Socket
66224887070/90140350Ball & Socket
662248870120140350Ball & Socket
1324495130590275650Ball & Socket
1324495145090275650Ball & Socket
13244951450120275650Ball & Socket
22075951885904601050Ball & Socket
22075952030904601050Ball & Socket
220759520301204601050Ball & Socket
220759521751204601050Ball & Socket
220759523801604601050Ball & Socket
220759525501604601050Ball & Socket
220759527201604601050Ball & Socket
4001302033351206501425Ball & Socket
4001302039101606501425Ball & Socket
4001302040801606501425Ball & Socket
7651240029001208302400Ball & Socket
7651240029751608302400Ball & Socket
7651240029751608302400Ball & Socket