Dead End Type Insulators

Insulator Section View 4
Insulator Data Table

Dead End Type Insulators – As per ANSI C 29.13 – 2018, IEC 61109 , IEC 62217 & IEC 60815

Type of Insulator Nominal System Voltage (kV) Min Creepage Distance (mm) Sectional Length (mm) Mechanical Load (kN) Low Frequency Dry Flash over (kV) Low Frequency Wet Flash over (kV) Positive Critical Impulse Flash over (kV)
DS-15 15 420 331 70 90 65 140
DS-28 28 650 430 70 130 100 190
DS-28 28 800 469 70 150 135 255
DS-35 35 1000 548 70 170 155 280
DS-46 46 1375 634 70 188 166 325